IG-541 mixed gas fire extinguishing system   

IG-541 mixed gas fire extinguishing system


 

IG-541 mixed gaseous extinguishing agent is mixed by nitrogen gas, gas and carbon dioxide gas at certain ratio. These gases are natural and influential on environment.

IG-541 mixed gas fire extinguishing system is composed by fire automatic detector, automatic fire alarm controller, automatic control device, fixed fire-extinguishing unit and pipeline and nozzle. It has 3 kinds of starting mode, including, automatic starting, manual starting and mechanical emergency starting.

 

 

Features

Environmental friendly: zero ODP and ALT;

No harm: fine electric insulation and no harm on people of scene of fire;

Clean: no residue after evaporation, no pollution;

High efficiency: fine fire extinguishing performance and long delivery distance;

 

 

Sites applicable

Coffers of financial system;
Computer room, post and telecommunication mansion, regulation and control center;
Scientific research institute, laboratory, test center, metrical study institute;
Museum, jewellery tower, library, historical relic hall, archives;

 

 

 

Radio and television center, television tower, television station, property building;
Electric power dispatching center, administration of power supply, power station and transformer substation;
Generator room, switch board room, transformer cabin, cable well, cable trench;
Turbine machine room and gas-fired boiler;
Storage and transportation center, warehouse, inflammable goods storage center;  

 

 

Main technical parameters

Extinguish fire technique: total flooding
Designed working pressure: 15Mpa
Decompression pressure: 20.7-+1.OMpa
Radius of protection of single nozzle: ≤5m
Protection height of nozzle: ≤6.5m
Mixed gas(ig541) blowing duration:≤60s
Mixed gas(ig541) filling rate:0.21kg/L
Mixed gas(ig541) reservoir vessel: 80L, 90L
Temperature for storage:-10~50℃

 

Square of conservation area: non-network fire extinguishing system≤500㎡, piping extinguishing system≤800㎡ 
Volume of conservation area: non-network fire extinguishing system≤1600m3, piping extinguishing system≤3600m3
Starting mode of system: automatic, manual and emergency operation
Starting power supply: DC24V,1.3A
N2 starting receiver volume:4.0L, 10L, 40L
N2 starting receiver filling pressure:6.OMPa
4.0L N2 starting receiver starting fire extinguishing agent bottles: ≤30 bottles
10L N2 starting receiver starting fire extinguishing agent bottles:≤50 bottles
40L N2 starting receiver starting fire extinguishing agent bottles:≤200 bottles 

 